APC Smart-UPS RT 10kVA 230V True-Tech
The APC Smart-UPS RT 10kVA 230V features:
Lead time | Usually in Stock |
---|
Run time for load
W information_stroke
Min-max: 1000-10000 W
|
3min 32s
|
---|---|
Max. Capacity Used
information_stroke
|
100 % |
Main Input Voltage | 230 V |
product or component type | Uninterruptible power supply (UPS) |
Other Input Voltage | 220 V 240 V |
Main Output Voltage | 230 V |
Other Output Voltage | 220 V 240 V |
Rated power in W | 10000 W |
Rated power in VA | 10000 VA |
output connection type | 2 IEC 60320 C13 1 IEC 60320 C19 |
Output connector type | Hard wire 3-wire (H N + E) 1 |
Number of rack unit | 5U |
Provided equipment | 1 x USB cable
|
Run Time |
View Runtime Graph
|
---|---|
Efficiency |
View Efficiency Graph
|
Battery type | Lead-acid battery |
Number of battery filled slots | 0 |
Number of battery free slots | 0 |
Battery recharge time | 4 h |
Number of battery replacement quantity | 2 |
Battery voltage | +/- 96 V |
Battery charger power | 431 W rated |
Battery life | 3…5 year(s) |
Replacement battery |
APCRBC174
|
Extended runtime | 1 |
UPS type | Double conversion online |
---|---|
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
Colour | Black (RAL 9005) |
---|---|
Height | 21.7 cm |
Width |
44 cm |
Depth | 68 cm |
net weight | 101.5 kg |
Mounting preference | No preference |
mounting mode | Rack-mounted with kit |
Two post mountable | 0 |
USB compatible | Yes |
Mounting position | Horizontal |
Network frequency | 40…70 Hz auto-sensing |
---|---|
Number of input connectors | 1 hard wire 3-wire (1P + N + E) |
Input voltage limits | 160…285 V full load |
Maximum input current | 30 A |
Max short time withstand current | 40 kA |
Maximum configurable power in VA | 10000 VA |
---|---|
Maximum configurable power in W | 10000 W |
Output frequency | 50/60 Hz +/- 4 Hz sync to mains |
Wave type | Sine wave |
Efficiency | 93.5 % |
Harmonic distortion | Less than 2 % |
Crest factor | 3 : 1 |
Bypass type | Internal bypass (automatic and manual) |
Additional information | Configurable for 220 : 230 or 240 nominal output voltage |
Product certifications | CE UKCA TISI |
---|---|
Standards | EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018 |
Ambient air temperature for operation |
0…40 °C |
---|---|
Relative humidity | 0…95 % non-condensing |
Operating altitude | 0…3000 m |
Ambient air temperature for storage | -15…45 °C |
Storage Relative Humidity | 0…95 % non-condensing |
Storage altitude | 0…15000 m |
Acoustic level | 55 dBA |
heat dissipation | 2217.98 Btu/h |
IP degree of protection | IP20 |
Preinstalled device | Network management card 3 with environmental
monitoring |
---|---|
Alarm | Alarm when on battery : distinctive low battery alarm :
overload continuous tone alarm |
Emergency power off | Yes |
Surge energy rate | 600 J |
---|
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 68.5 cm |
Package 1 Width | 59.4 cm |
Package 1 Length | 79.4 cm |
Package 1 Weight | 124.5 kg |
Warranty | 3 years repair or replace (excluding battery) and 2 years for battery |
---|